Velox Power cable 5 x 25mm² Grounding cable
|
Standards
DIN VDE 0276-603, part 3G/HD 603.1 and IEC 60502-1. The cables are in compliance with EU LVD (Low voltage Directive 73/23 EEC) and RoHS Directive EU 2011/65, RoHS 2.0 and Regulation No. 1907/2006 (REACH).
They are flame retardant and self-extingishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting propertis of lacquers.
Technical Data
Rated voltage | kV | 0,6/1 |
Test voltage | kV | 4 |
Installation temperature during laying (min) after laying (max) |
°C | -5 +70 |
Short-circuit temperature | °C | +160 |
Max. permissible operating temperature (conductor) | °C | +70 |
Cable marking
Part.no: | Denomination/Marking: |
VX314-25 | Grounding cable 5x25mm² Grounding cable (NYY-J 4×120 SM 0,6/1 Kv) |
Area of use
For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected (see DIN VDE 0298-1).
The cables are insensitive to occasional impacts of oils and fuels
Type Designation codes
N | Cbles acc. to standard |
(N) | Cables based on standard |
Y | insulation made of polyvinyl chloride (PVC) |
Y | Outer sheath made of polyvinyl chloride (PVC) |
J- | Cble with green-yellow core |
RE | circular conductor, solid |
RM | circular conductor, stranded |
SM | sector-shaped conductor, stranded |
Special designs
- Design according to national and international standards
- Design according to customer specification
- Design with limited tolerance of outer diameter on request
Part.no | Product | Cu-number kg/km |
Outer dimension Ø approx. mm |
Net weight approx. kg/km |
Rated current kA |
Max. tension load daN |
Bending radius min. mm |
Bending radius mehm min. mm |
VX314-25 | Power cable 5x25mm² | 1200 | 30 | 1980 | 2.88 | 625 | 180 | 360 |