Velox Power cable 5 x 16mm²

Velox Power cable 5 x 16mm² Grounding cable

matarkabel

  1. Outer sheath, PVC black
  2. Extruded inner covering
  3. Cores concentric stranded
  4. Core colours acc. to VDE 0293
  5. PVC-Insulation
  6. Solid or stranded copper conductor

Standards

DIN VDE 0276-603, part 3G/HD 603.1 and IEC 60502-1. The cables are in compliance with EU LVD (Low voltage Directive 73/23 EEC) and RoHS Directive EU 2011/65, RoHS 2.0 and Regulation No. 1907/2006 (REACH).

They are flame retardant and self-extingishing according to DIN EN 50265-2-1 (IEC 60332-1-2) and free of silicone, cadmium and free from substances harmful to the wetting propertis of lacquers.

Technical Data

Rated voltage  kV 0,6/1
Test voltage kV 4
Installation temperature
during laying (min)
after laying (max)
°C -5
+70
Short-circuit temperature °C +160
Max. permissible operating temperature (conductor) °C +70

Cable marking

Part.no: Denomination/Marking:
VX313-16 Power cable 5x16mm² Grounding cable (NYY-J 5x16 SM 0,6/1 Kv)
Area of use

For indoor and outdoor installation, in the ground, for power stations, industry and distribution boards or subscriber networks, where mechanical damage to the cable is not expected (see DIN VDE 0298-1).

The cables are insensitive to occasional impacts of oils and fuels

Type Designation codes

N Cbles acc. to standard
(N) Cables based on standard
Y insulation made of polyvinyl chloride (PVC)
Y Outer sheath made of polyvinyl chloride (PVC)
J- Cble with green-yellow core
RE circular conductor, solid
RM circular conductor, stranded
SM sector-shaped conductor, stranded

Special designs

  • Design according to national and international standards
  • Design according to customer specification
  • Design with limited tolerance of outer diameter on request
Part.no Product Cu-number
kg/km
Outer dimension Ø
approx. mm
Net weight
approx. kg/km
Rated current
kA
Max. tension load
daN
Bending radius
min. mm
Bending radius mehm
min. mm
VX313-16 Power cable 5x16mm² 768 24 1290 1.84 400 150 300